Condenser
On air--cooled Chillers, the CONDENSER FINS should be cleaned by blowing compressed air through the con-
denser from the fan side. Dirt and debris accumulate on the condenser fins over time, and this build up can se-
verely reduce the performance of the Chiller. Cleaning of the CONDENSER COIL FINS should be done
approximately every three months, depending upon cleanliness of your application.
Fan Motor
On air--cooled Chillers, the condenser FAN MOTOR should be lubricated every 6 months with a few drops of
SAE 10 oil.
Pump Motor
The PUMP MOTOR should be lubricated with thirty drops of SAE 20 oil once a year.
Circulation System
The CIRCULATION SYSTEM should be drained and flushed periodically to avoid build up and a possible flow
restriction caused by contaminants.
Filters/Strainers
The STRAINER at the Chiller inlet should be removed and cleaned monthly.
The “Y” STRAINER, located inside the unit at the inlet of the pump, should be cleaned periodically depending on
applications. If a reduction in flow or cavitation of the pump occurs, remove the strainer, flush it out with water,
then replace.