620914301
TROUBLE REMEDYPROBABLE CAUSE
CHILLER DOES NOT
OPERATE, BUT POWER
LIGHT IS “ON” AND RED
SAFETY LIGHT IS “ON”.
A. Unit is operating under high
pressure conditions.
A. Check for dirty condenser fins or
obstruction of chiller air intake.
Press high pressure manual reset
switch. If this problem persist,
contact Remcor Service
Department.
B. Unit is operating under low
temperature conditions.
B. Low or no process liquid flow.
Ensure that there is adequate flow
through system plumbing.
or
Process liquid is too cold, below
35_ F. Increase thermostat setting
or bypass valve stuck open.
Replace solenoid valve. Check for
proper voltage.
or
Defective thermostat, replace.
C. Unit has experienced low flow
condition (LX and EX units).
C. Check for obstruction in process
liquid line plumbing.
NOTE: When servicing a REMCOR Chiller, it is important to note all information provided on the DATA
PLATE located in the upper rear of the unit. If technical assistance is needed, the REMCOR Service
Technician will need this information along with any description of the problem(s) you are
encountering. The serial number and other information will also be required when ordering
replacement parts and any other Warranty Claims.