When servicing a REMCOR Chiller, it is important to note the information contained on the data plate located in
the upper rear of the Unit.
If technical assistance is needed, the phone technician will need the Serial Number of your Chiller . That informa-
tion is found on the Data Plate along with the model number, voltage requirement, and refrigerant information.
The serial Number is also needed when replacement parts are being ordered or for warranty claims. See
CHILLER WARRANTY PAGE.
Be sure to include the serial number on any documentation or billing information.
CHILLER INSTALLATION
Location of Chiller
(see Figure 2)
THE CHILLER MUST BE LOCATED NEAR A PROPERLY GROUNDED ELECTRICAL OUTLET. THE CIR-
CUIT SHOULD BE FUSED AND NO OTHER ELECTRICAL APPLIANCE SHOULD BE CONNECTED TO THE
CIRCUIT. ALL ELECTRICAL WIRING MUST CONFORM TO NATIONAL AND LOCAL ELECTRICAL
CODES.
The Chiller must be located in a well ventilated, indoor area where ambient temperatures will remain above
40_ F(5_ C) and will never increase above 100_ F(38_ C). To obtain optimum cooling capacity, the ambient
temperature should be at or below 80_ F(27_ C).
It is very important that the air intake and discharge sides of the chiller are not obstructed by other free standing
objects. A minimum of two feet of space on all four sides of the chiller will be sufficient to prevent air flow
obstructions.
It is also important to direct any hot air discharge from other equipment away from the air intake side of the chill-
er. Condenser air entering the “CH” unit should be below 100_ F(38_ C) .Condenser air temperatures above
100_ F(38_ C) can cause the high pressure safety control to shut down the unit.
FIGURE 2. INSTALLATION
26--13/16
19--7/16
37--5/16
37--11/16
30--1/2
21--15/16
CONTROL
PANEL
FRONT VIEW SIDE VIEW REAR VIEW
FILL PORT
RESERVOIR
LEVEL
INDICATOR
PRESS
GAUGE
DRAIN VALVE AND
PLUG (BEHIND PANEL)
INLET
OUTLET
JUNCTIO N BOX